Product overview
EP3356-0022
9
Version: 1.4
2.2
EP3356-0022 - Technical data
Technical data
EP3356-0022
Number of inputs
2, for 1 resistor bridge in full bridge technology
M12
Resolution
24 Bit, 32 bit presentation
Conversion time
0.1 ms…250 ms, configurable, max. 10,000 samples/s
Nominal voltage
24 V
DC
(-15 %/+20 %)
Distributed Clocks
yes
selectable modes
yes (2)
Measuring error
<±0.01 % for the calculated load value in relation to the final load value
with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge
characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active.
Attention: Due to external influences such as
and HF-disturbances may possibly occur a not insignificant error!
Measuring range U
D
max. -27 mV…+27 mV typ. (see
concerning voltage
measuring recommended: -25 mV…+25 mV rated voltage
Measuring range U
ref
max. -13.8 V…+13.8 V typ. (see
concerning voltage
measuring recommended: -12 V…+12 V rated voltage
Supported nominal sensitivity
all, resolution of parameter: 0.01 µV/V
Recommended: 0.5 mV/V…4 mV/V
Min. strain gauge resistor
parallel operation of strain gauges only with suitable strain gauges
recommended
Input filter limit frequency
(hardware)
10 kHz low pass (-3 dB)
Filter (software)
Present 50 Hz,
Configurable: 50/60 Hz FIR notch filter, IIR low pass 4-fold averager
Internal resistance
>200 kΩ (U
ref
), > 1 MΩ (U
d
)
Special features
self-calibration, quadruple averager, dynamic filters, fast data sampling,
parallel connection
Sensor supply U
ref
U
ref
= 10 V (supplied by the EP3356 from U
P
)
max. 350 mA
Current consumption from U
S
(without sensor current)
120 mA
Power supply connection
feed: 1 x M8 male socket, 4-pin
downstream connection: 1 x M8 female socket, 4-pin
Permissible ambient temperature
during operation
-25 .. +60 °C
-25 .. +55 °C (according to cURus, see
)
Permissible ambient temperature
during storage
-40°C…+85°C
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Dimensions
126 mm x 60 mm x 40 mm
Weight
approx.. 450 g
Installation position
variable
Protection class
IP65, IP66, IP67 (according to EN 60529)
Approvals
CE, cURus