Commissioning/Configuration
EP3356-0022
65
Version: 1.4
Input data, Index 6000 RMB Inputs
Index (hex) Name
Meaning
Data type
Flags
Default
6000:0
RMB Inputs
Max. subindex
UINT8
RO
0x13 (19
dec
)
6000:02
Overrange
The measuring value has reached its terminal/
box value
BOOLEAN
RO
0x00 (0
dec
)
6000:04
Data invalid
The indicated process data are not valid, e.g. dur-
ing calibration
BOOLEAN
RO
0x00 (0
dec
)
6000:07
Error
An error has occurred
BOOLEAN
RO
0x00 (0
dec
)
6000:08
Calibration in progress
Calibration in progress. The process data indicate
the last valid measuring value
BOOLEAN
RO
0x00 (0
dec
)
6000:09
Steady state
BOOLEAN
RO
0x00 (0
dec
)
6000:0E
Sync error
TRUE: In the last cycle the synchronization was
not correct (only in DC-Mode)
BOOLEAN
RO
0x00 (0
dec
)
6000:10
TxPDO Toggle
The TxPDO Toggle is toggled by the slave, if the
data of the corresponding PDO was updated.
BOOLEAN
RO
0x00 (0
dec
)
6000:11
Value
Measuring value as 32 Bit SIGNED INTEGER
INT32
RO
0x61746144
(1635017028
dec
)
6000:12
Value (Real)
Measuring value as REAL
REAL32
RO
0x00000000
(0
dec
)
6000:13
Timestamp
Timestamp of current measuring value (only
EL3356-0010/EP3356-0022 in DC-Mode)
UINT64
RO
Input data Index 6010, 6020 AI Inputs
Index (hex) Name
Meaning
Data type
Flags
Default
60n0:0
AI Inputs
Max. subindex
UINT8
RO
0x11 (17
dec
)
60n0:01
Underrange
Value falls below the measuring range
BOOLEAN
RO
0x00 (0
dec
)
60n0:02
Overrange
Measurement range is exceeded.
BOOLEAN
RO
0x00 (0
dec
)
60n0:07
Error
An error has occurred, e.g.:
- Over- / underrange U
dif
- Over- / underrange U
ref
- the external U
ref
is too low (between-1 V and
+1 V)
- Data invalid
BOOLEAN
RO
0x00 (0
dec
)
60n0:10
TxPDO Toggle
The TxPDO Toggle is toggled by the slave, if the
data of the corresponding PDO was updated.
BOOLEAN
RO
0x00 (0
dec
)
60n0:11
Value
32 Bit measuring value
INT32
RO
0x00000000
(0
dec
)
Output data, Index 7000 RMB Outputs
Index (hex) Name
Meaning
Data type
Flags
Default
7000:0
RMB Outputs
Max. subindex
UINT8
RO
0x05 (5
dec
)
7000:01
Start calibration
The calibration can be started manually with a ris-
ing edge.
Therefore, an automatic start of the calibration at
an inappropriate point of time can be prevented.
BOOLEAN
RO
0x00 (0
dec
)
7000:02
Disable calibration
0: The automatic calibration is active
1: The automatic calibration is inactive
BOOLEAN
RO
0x00 (0
dec
)
7000:03
Input freeze
The process data and the digital filter will be
frozen
BOOLEAN
RO
0x00 (0
dec
)
7000:04
Sample mode
Selection of the sampling mode:
0: 10.5 kHz High precision
1: 105 kHz Low latency
BOOLEAN
RO
0x00 (0
dec
)
7000:05
Tara
The process data can be set to zero with a rising
edge.
The tara value is not stored in the EEPROM and
is lost after a reset of the terminal/box
BOOLEAN
RO
0x00 (0
dec
)
7000:11
Filter frequency
Filter frequency of the variable PDO filter in
0.1 Hz, see
Wertebereich:
value range: 1 ... 2000 (equates to 0,1 ... 200 Hz)
From a value 0 or >2000, the filter behaves like a
50 Hz FIR filter
UINT16
RO
0x00 (0
dec
)