Mounting and Cabling
EP3356-0022
22
Version: 1.4
4.3
Supply voltages
The EtherCAT Box is supplied with two supply voltages. The supply voltages are electrically isolated in the
EtherCAT Box.
• Control voltage U
S
• Peripheral voltage U
P
Redirection of the supply voltages
The IN and OUT power connections are bridged in the module (not IP204x-Bxxx and IE204x). The supply
voltages U
S
and U
P
can thus easily be transferred from EtherCAT Box to EtherCAT Box.
NOTE
Pay attention to the maximum permissible current!
Pay attention also for the redirection of the supply voltages U
S
and U
P
, the maximum permissible current for
M8 connectors of 4 A must not be exceeded!
4.3.1
Connectors
NOTE
Risk of confusion: supply voltages and EtherCAT
Defect possible through incorrect insertion.
• Observe the color coding of the connectors:
black: Supply voltages
green: EtherCAT
Fig. 12: Connectors for supply voltages
Plug
Input
Socket
Forwarding
3
1
2
4
3
1
2
4
Fig. 13: M8 connector
Contact
Function
Description
Core color
1)
1
U
S
Control voltage
Brown
2
U
P
Peripheral voltage
White
3
GND
S
GND to U
S
Blue
4
GND
P
GND to U
P
Black
1)
The core colors apply to cables of the type: Beckhoff ZK2020-3xxx-xxxx
Содержание EP3356-0022
Страница 2: ......
Страница 79: ...Commissioning Configuration EP3356 0022 79 Version 1 4 Fig 49 Confirming program start ...
Страница 90: ......