Commissioning/Configuration
EP3356-0022
57
Version: 1.4
Function of the variables
Variable
: Status
Meaning
: The status word (SW) is located in the input process image, and is transmitted from box to the
controller.
Bit
SW. 15
SW.
14
SW. 13 SW.
12
SW.
11
SW.
10
SW.
9
SW. 8
SW. 7
SW. 6 SW.
5
SW.
4
SW. 3
SW.
2
SW. 1
SW.
0
Name
TxPDO Tog-
gle
-
Sync Er-
ror
-
-
-
-
Steady
State
Calibra-
tion in
progress
Error
-
-
Data in-
valid
-
Overrange
-
Mean-
ing
Toggles
0→1->0
with each
updated
data set
-
Syn-
chroni-
sation
error
progress
Col-
lective
error
dis-
play
-
-
Input
data are
invalid
-
Measuring
range ex-
ceeded
-
Variable
: Value
Meaning
: Calculated 32-bit DINT load value in unit [1], with sign
Variable
: Value (Real)
Meaning
: Calculated 32-bit fixed point REAL load value with mantissa and exponent in unit [1]
The format matches the REAL format of IEC 61131-3, which in turn is based on the REAL format of IEC 559.
A REAL number (single precision) is defined as follows (See also Beckhoff InfoSys:
). In accordance with IEC 61131 this 32-bit variable can be directly linked with a FLOAT
variable of the PLC.
Bitposition (from the left)
1
8
23 (+1 „hidden bit“, see IE559)
Function
Sign
Exponent
Mantissa
Variable
: WcState
Meaning
: Cyclic diagnostic variable; „0“ indicates correct data transmission
Variable
: Status
Meaning
: State of the EtherCAT device; State.3 = TRUE indicates correct operation in OP
Variable
: AdsAddr
Meaning
: AmsNet address of the EtherCAT device from AmsNetId (in this case: 192.168.0.20.5.1) and port
(in this case: 1003)