Commissioning/Configuration
EP3356-0022
63
Version: 1.4
Index (hex) Name
Meaning
Data type
Flags
Default
8000:23
Rated output
Nominal sensitivity of sensor element in mV/V
REAL32
RW
0x40000000
(1073741824
dec
)
= 2.0
8000:24
Nominal load
Nominal load of force transducer/load cell/etc.
(e.g. in kg or N, ....)
REAL32
RW
0x40A00000
(1084227584
dec
)
= 5.0
8000:25
Zero balance
Zero point offset in mV/V
REAL32
RW
0x00000000
(0
dec
) = 0.0
8000:26
Gravity of earth
Current gravity of earth (default 9.806650)
REAL32
RW
0x411CE80A
(1092413450
dec
)
= 9.806650
8000:27
Scale factor
This factor is for rescaling of the process data,
e.g. for changing the indication from "kg" to "g",
you shall enter the factor "1000" here.
REAL32
RW
0x447A0000
(1148846080
dec
)
= 1000.0
8000:28
Reference load
Reference weight for manual calibration
REAL32
RW
0x40A00000
(1084227584
dec
)
= 5.0
8000:29
Steady state window
Time constant for the "steady state" bit (
)
UINT16
RW
0x03E8
(1000
dec
)
8000:2A
Steady state tolerance
Tolerance window for the "steady state" bit
UINT32
RW
0x00000005
(5
dec
)
8000:31
Calibration interval
Calibration interval for the automatic calibration of
the terminal/box (unit: 100 ms)
The automatic calibration can be prevented by
setting the process data bit "Disable calibration"
UINT16
RW
0x0708
(1800
dec
)
8000:32
Test interval
This object contains the testing interval for the
cyclic self test of the terminal/box
This interval is always a multiple (default: 10
dec
) of
the calibration interval (0x8000:31So the delivery
state of the testing interval result from 10 x 180 s
= 1800 s.
The self test can be prevented by setting the
process data bit "Disable calibration"
UINT16
RW
0x000A (10
dec
)