6.2.1
User \CIRCA0 menu
Tab.13 CP : Circuits Parameters = Heating circuit parameters
Parameter
Description
Factory setting
CP010
Zone flow temperature setpoint, used when the zone is set to a fixed flow
setpoint.
75
CP080
Reduced room temperature set point (Eco)
Can be set from 5 °C to 30 °C
16
CP081
Comfort room temperature set point (On)
Can be set from 5 °C to 30 °C
20
CP140
Reduced cooling set point temperature (Eco)
Can be set from 20 °C to 30 °C
30
CP141
Comfort cooling set point temperature (On)
Can be set from 20 °C to 30 °C
25
CP200
Manually setting the RoomTemperature setpoint of the zone
Can be set from 5 °C to 30 °C
20
CP320
Operating mode of the zone
0 = timer programming
1 = manual mode
2 = frost protection mode
0
CP510
Temporary room setpoint per zone
Can be set from 5 °C to 30 °C
20
6.2.2
User \DHW menu
A domestic hot water sensor must be connected to the EHC–05 board to
display these parameters.
Tab.15 DP : Direct Hot Water Parameters = Domestic hot water tank parameters
Parameter Description
Factory setting
DP060
Time program selected for DHW.
0 =Schedule 1
1 =Schedule 2
2 =Schedule 3
0
DP070
Comfort temperature setpoint from the Domestic Hot Water tank
Can be set from 40 °C to 65 °C
54
DP080
Reduced temperature setpoint from the Domestic Hot Water tank
Can be set from 10 °C to 60 °C
30
DP200
DHW primary mode current working setting
0 =Scheduling
1 =Manual
2 =Antifrost
0
DP337
Holiday temperature setpoint from the Domestic Hot Water tank
Can be set from 10 °C to 60 °C
30
6.2.3
User \ CIRCA1, CIRCB1, DWH1, CIRCC1, CIRCAUX1
menu
Depending on the installation configuration, only certain circuits are
available. The CIRCA1, CIRCB1, DWH1, CIRCC1, CIRCAUX1 circuits are
on the SCB-10 PCB.
6 Settings
20
iHPI
7701562 - v02 - 22052018