AM012 =Status Appliance
AM014 =Appliance sub status
8= controlled compressor
shut-down
00= off: the heating or cooling set point has been reached
01= anti-short cycle
The heating set point has been reached. The compressor is not authorised to restart.
60= pump post-operation
Heat pump and back-up shut-down, system pump post-operation.
67= the outside temperature is lower than the compressor's maximum operating tempera
ture
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
75= compressor shut-down owing to the condensation detector
76= compressor shut-down owing to the flow rate
79= compressor and back-up bypass in heating / domestic hot water mode
80= compressor and back-up bypass in cooling mode
82= temperature lower than the minimum cooling temperature
Compressor shut-down.
9 =Blocking Mode
30= normal operation.
The compressor or the back-ups are running.
31= internal set point limited
If the heating set point on the heat pump differs from the system set point.
60= pump post-operation
Heat pump and back-up shut-down, system pump running.
65= compressor bypass
The back-ups are operating.
66= the temperature exceeds the compressor's maximum operating temperature
The compressor has stopped. The back-ups are operating.
67= the outside temperature is lower than the compressor's maximum operating tempera
ture
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
69= defrosting running
The compressor is running.
70= defrosting conditions not met
The compressor has stopped. The back-ups are operating.
71= defrosting running.
The compressor and the back-ups are running.
10
Locking Mode
12 =Load test CH max
30= normal operation. The compressor or the back-ups are running.
31= internal set point limited
If the heating set point on the heat pump differs from the system set point.
60= pump post-operation
Heat pump and back-up shut-down, system pump post-operation.
65= compressor bypass and back-ups running
66= the temperature exceeds the compressor's maximum operating temperature
The compressor has stopped. The back-ups are operating.
67= the outside temperature is lower than the compressor's maximum operating tempera
ture
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
69= defrosting running
The compressor is running.
70= defrosting conditions not provided
The compressor has stopped. The back-ups are operating.
71= defrosting running.
The compressor and the back-ups are running.
6 Settings
7701562 - v02 - 22052018