Tab.16 CP : Circuits Parameters = Heating circuit parameters
Parameter
Factory setting for each circuit
Description
CP010
CP011
CP012
CP013
CP014
CIRCA1: 75
CIRCB1: 40
DHW1: 75
CIRCC1: 40
CIRCAUX1: 75
Zone flow temperature setpoint, used when the zone is set to a fixed flow
setpoint.
Can be set from 7 °C to 100 °C
CP080
CP086
CP098
CIRCA1: 16
CIRCB1: 16
CIRCC1: 16
Reduced room temperature set point (Eco)
Can be set from 5 °C to 30 °C
CP081
CP087
CP099
CIRRA1: 20
CIRCB1: 20
CIRCC1: 20
Comfort room temperature set point (On)
Can be set from 5 °C to 30 °C
CP140
CP146
CP158
CIRCA1: 30
CIRCB1: 30
CIRCC1: 30
Reduced cooling set point temperature (Eco)
Can be set from 20 °C to 30 °C
CP141
CP147
CP159
CIRCA1: 25
CIRCB1: 25
CIRCC1: 25
Comfort cooling set point temperature (On)
Can be set from 20 °C to 30 °C
CP144
CP150
CP162
CIRCA1: 25
CIRCB1: 25
CIRCC1: 25
Heating curve temperature gradient of the zone
Can be set from 0 to 4
CP200
CP201
CP203
CIRCA1: 20
CIRCB1: 20
CIRCC1: 20
Manually setting the RoomTemperature setpoint of the zone
Can be set from 5 °C to 30 °C
CP320
CP321
CP322
CP323
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
Operating mode of the zone
0 =Scheduling
1 =Manual
2 =Antifrost
3 =Temporary
CP352
DHW1: 55
Comfort Domestic Hot Water Temperature Setpoint of zone
Can be set from 40 °C to 80 °C
CP362
DHW1: 10
Reduced Domestic Hot Water Temperature Setpoint of zone
Can be set from 10 °C to 60 °C
CP510
CP511
CP512
CP513
CIRCA1: 20
CIRCB1: 20
DHW1: 20
CIRCC1: 20
Temporary room setpoint per zone
Can be set from 5 °C to 30 °C
CP540
CP541
CP543
CIRCA1: 20
CIRCB1: 20
CIRCC1: 20
Setpoint of swimming pool when Zone is configured on SwimmingPool
Can be set from 0 °C to 39 °C
6.2.4
User \ EHC–05 and SCB-10 menu
Tab.18 AP : Appliance Parameters = Appliance parameters
Parameter Description
Factory setting
EHC–05
Factory setting
SCB-10
AP015
Force manually the heat pump in cooling mode
0 =No
1 =Yes
0
not available
AP016
Enable central heating heat demand processing
0 =Off
1 =On
1
not available
AP017
Enable domestic hot water heat demand processing
0 =Off
1 =On
1
not available
6 Settings