1. Access the domestic hot water production parameters by pressing the
key.
2. Modify the domestic hot water temperature set point by pressing the
or key.
Important
Press the
h
key to cancel all input.
3. Confirm the new temperature set point by pressing the
key.
Go back to the main display by pressing the
h
key.
6.4.3
Activating Forcing of the cooling function
The cooling function can be managed via the PROG COOL sub-menu
dedicated to timer programming.
The set point flow temperature for cooling mode corresponds to the
CP270 parameter for underfloor heating and CP280 for a convection fan.
The CP270 and CP280 parameters can be accessed by the Installer.
Important
The heat pump switches to cooling automatically when the
outdoor temperature is +2 °C greater than the summer/winter
switching set point temperature (22 °C). The forced cooling
function is used to have cooling regardless of the outdoor
temperature.
1. Access Forcing of the cooling function by pressing the
key.
Important
Forcing of the cooling function is possible only if the Installer
enabled the cooling function during Installation.
2. Access Forcing of the cooling function by pressing the
key.
3. Activate Forcing of the cooling function by pressing the key.
Fig.30
MW-6000254-2
Fig.31
MW-5000401-2
Fig.32
MW-5000402-2
Fig.33
MW-5000403-2
6 Settings
26
iHPI
7701562 - v02 - 22052018