Measurement
Description
Unit
EHC–05
DM006
Domestic Hot Water tank temperature (top sensor)
°C
X
DM009
Automatic/derogation status of Domestic Hot Water mode:
0 =Scheduling
1 =Manual
2 =Antifrost
3 =Temporary
°C
X
DM029
Domestic Hot Water temperature setpoint
°C
X
Tab.32 Available values: HM = Heat-pump Measures = Measured values for the heat pump
Value
Description
Unit
EHC–05
HM001
Heat pump flow temperature after condenser
°C
X
HM002
Heat pump return temperature after condenser.
°C
X
HM003
Outdoor unit set point temperature
°C
X
HM004
Heat pump blocking input1
/
X
HM005
Heat pump blocking input2
/
X
HM007
Heat Pump Error State
/
X
HM008
Compressor operation
/
X
HM009
Heat Pump Defrost
/
X
HM012
First stage of backup operation
/
X
HM013
Second stage of backup operation
/
X
HM030
Status if the compressor is in starting request or not.
/
X
HM033
Water set point temperature in cooling mode
/
X
HM046
5 V set point signal sent to the heat pump
/
X
HM069
Heat pump condenser pump speed.
/
X
HM070
Heat pump condenser pump operating status
/
X
Tab.33 Values available (X) in the
sub-menu
Value
Description
EHC–05
SCB-10
CXX.XX
Software version for the EHC–05 PCB
X
FXX.XX
Software version for the SCB-10 PCB
X
PXX.XX
Parameter version for the EHC–05 PCB
X
VXX.XX1
Software version for the SCB-10 PCB
X
6.5.2
Control system sequence
Tab.34 List of statuses and sub-statuses
AM012 =Status Appliance
AM014 =Appliance sub status
0 =Standby
00= total system shut-down
1 =Heat Demand
00 = off
The set point is reached. The compressor can start up whenever necessary.
01= anti-short cycle
The heating set point has been reached. The compressor is not authorised to restart.
02= reversal valve switch to heating position
03= power supply to the hybrid pump
04= pending start-up conditions on the heat pump and the back-ups
62= three-way valve switch to domestic hot water position
6 Settings
7701562 - v02 - 22052018
iHPI
31