PROFIBUS
112
Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
DaAdr $57: EquipmentControlStatus
Format: Char
7
6
5
4
3
2
1
0
Free
Free
ExternWater
Error
Free
Free
Free
InternWater
Error
Free
ExternWater: 1 = External level s
ensor reports „no water“
InternWater Error:
1 =
Internal level control reports „no water“
If the corresponding inputs in EquipmentChConfig (DaAdr $4C) have not
been released, the status bits are left at '0'.
DaAdr $58: EquipmentChConfig
Format: Char
Before you can write this variable you must first change to standby mode.
7
6
5
4
3
2
1
0
Free
Free
External
water
detector
Free
Free
Free
Internal
water
detector
Free
0
Default
0
0
0
0
0
1
0
Releases the corresponding monitoring of the water level.
DaAdr $53: Limit Task Config
Format: Char [2]
Char [1] : 0x00 = Limit monitoring not active
0x01 = Limit monitoring active
Char [2] : Value for the measurand to be taken over.
0
TT
8
VP
1
HT
9
MH
2
SP
10 SH
3
DP
11 H
4
T1
extern
12 DVP
5
T
intern
13 RH
extern
6
DT
14 Vol%
7
RH