Programming
68
Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
5.2.4.5
Compressed air control
If the air flow rate is controlled by external units that are available on the
premises of the system operator, the integrated compressed air control must
be switched off. This prevents any faults concerning this control from being
reported.
The operator of the system is responsible for ensuring that the correct gas
flow rate is observed.
ENTER
Don’t make any changes
1
Switch on compressed air control
0
Switch off compressed air control
This is so that the differential pressure value of 500 Pa as standard can be
changed to a customer-specified value.
ENTER
No changes made
1
Change parameters
0
Do not change parameters
Enter the desired target value of the differential pressure here
(400 - 5
00 Pa … 999 Pa).
The value defines the maximum and minimum permitted deflection of the DP
actual value before a warning is generated.
Example
DP = 500 Pa,
DPRANGE = 100 Pa,
DPmax = 600 Pa, DPmin = 400 Pa
EQUIPM.-CONFIG
FLOW-CONTR. ? 1/0
EQUIPM.-CONFIG
- = 50
EQUIPM.-CONFIG
DP = 500
EQUIPM.-CONFIG
SET FLOW ? 1/0