Programming
66
Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
5.2.4
Programming the equipment
configuration
0
or
ENTER
Don’t make any changes, go to the next menu (limit
monitoring)
1
Change
the
programming
of
the
equipment
configuration
5.2.4.1
Temperature sensors
HYGROPHIL H 4230 contains two temperature measuring circuits for the
following temperature ranges: T1
external
:
0...200 °C
T
internal
:
0...100 °C.
The temperature measuring circuits are designed for the connection of
PT 100 temperature sensors and can be used as you wish.
T1
external
is an external temperature sensor. In order to measure temperature-
related humidity variables (RH, h) you must install the T1
external
temperature
sensor in the place where the humidity variable is to be measured.
ENTER
Don’t make any changes
1
Switch on temperature sensor T1
external
0
Switch off temperature sensor T1
external
Temperature sensor T
internal
is installed permanently in the enclosure. It is
used to compensate the humid temperature (HT).
ENTER
Don’t make any changes
1
Switch on temperature sensor T
internal
0
Switch off temperature sensor T
internal
The internal temperature sensor should always be switched on in
standard use of the device!
5.2.4.2
Safety switch-
off („TIMEOUT”)
You can program HYGROPHIL 4230 in such a way that it switches off
following a defined time after a fault occurs (TIMEOUT).
You can restart the equipment following a „TIMEOUT“ by pressing the
RESET
key or by disconnecting the equipment from the mains and then
connecting it again.
Attention:
If the equipment switches off automatically for safety reasons, you should
immediately attempt to locate the cause. If it is not possible to rectify the
fault straightaway, switch off the equipment and the compressed air supply.
0
or
ENTER
Don’t make any changes, go to the next menu (water
detector)
1
Change TIMEOUT programming
ENTER
Don’t make any changes
Change the time for automatic switch-off: enter a new value in seconds
using the keyboard,
ENTER
(600...3599)
EQUIP.CONF. ?
1/0
EQUIPM.-CONFIG
T1 extern ? 1/0
EQUIPM.-CONFIG
TIMEOUT ? 1/0
EQUIPM.-CONFIG
TIMEOUT [s] = 1200
EQUIPM.-CONFIG
T internal ? 1/0
Содержание HYGROPHIL H 4230-10 A Series
Страница 2: ......
Страница 51: ...Installation 45 Operating Instructions HYGROPHIL H 4230 10 Serie A BA 030520...
Страница 122: ...Operating Instructions HYGROPHIL H 4230 10 Serie A BA 030520...