PROFIBUS
103
Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
8.3
Channel description
8.3.1
Service channel
DaAdr (hex)
Identifier
Memory type
Read-out
Format
$03
Reset
RAM read/write
hex
Char
$0A
Status field
RAM read
bin. or hex
Long
$0B
Standby mode
RAM read/write
hex
Char
DaAdr $03: Reset
Format: char
Writing 0xFF triggers reset on the entire equipment (including PROFIBUS
interface)
DaAdr $0A: Status field
Format: long
Bit
0: DT low
Bit
1: DT high
Bit
2: TT low
Bit
3: TT high
Bit
4: DP low (flow too low)
Bit
5: DP high (flow too high)
Bit
6: HT low
Bit
7: HT high
Bit
8: Open error (proportional valve cannot open any further)
Bit
9: Close error (proportional valve cannot close any further)
Bit 10: Error in internal water detector
Bit 11: Error in external water detector
Bit 12: Hose error
Bit 13: Error timeout
Bit 14: Reserved
Bit 15: Equipment in standby mode
Bit 16: Flow min
Bit 17: Flow max
Bit 18: T1
external
out of range
Bit 19: T
internal
out of range
Bit 20: SP outrange
Bit 21: Reserved
Bit 22: Reserved
Bit 23: Out of Range
Bit 24: Analog output 1 underrange
Bit 25: Analog output 1 overrange
Bit 26: Analog output 2 underrange
Bit 27: Analog output 2 overrange
Bit 28: LOW LIMIT ERROR
Bit 29: HIGH LIMIT ERROR
DaAdr $0B: Standby mode
Format: char
Equipment changes to standby mode with 0x50.
Return to normal operation with 0x05.