PROFIBUS
108
Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
DaAdr $3B: Fullscale
Format: Array [1...2] of Float
Before you can write this variable you must first change to standby mode.
Setpoint value that corresponds to 100% in the output.
Default:
Setpoint [x]
Designation/unit
Value
1
DT/°C
100
2
HT/°C
100
DaAdr $3C: Zeropoint
Format: Array [1...2] of Float
Before you can write this variable you must first change to standby mode.
Setpoint value that corresponds to 0% in the output.
Default:
Zeropoint [x]
Designation/unit
Value
1
DT/°C
0
2
HT/°C
0
8.3.5
1-channel parameters
DaAdr (hex)
Identifier
Memory type
Read-out
Format
$40
Heating_w
EERPOM read/write
dec
Float
$41
Heating_xp
EERPOM read/write
dec
Float
$42
HeatingControlStatus
RAM read/write
-----
Record
$46
ErrorTime
EEPROM read/write
dec
Integer
$47
HT without comp
RAM read
dec
Float
$48
T2 correct config
EEPROM read/write
dec
Char
DaAdr $40: Heating_w
Format: Float
Before you can write this variable you must first change to standby mode.
Setpoint value w for the hose heating control (actual value =TT).
Default = 120°C
DaAdr $41: Heating_xp
Format: Float
Before you can write this variable you must first change to standby mode.
Proportional range xp in %.
Default = 3%