Setup, Network and Communication Manual ESTM / ESTM-L
17-88C1-*
11-88C1-7D0002
Notice
Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
Page 23 / 35
Controlled by
Function
Description
action / - effects on
Average:
Booth measured values are summed up in divided
by two to get the Actual value for the Control
only in availed sensor mode both sensors
Process control Value
see 4.8.1 Controller
Sensor 1:
sensor TC1 is used for Control. Sensor TC2 (If
both sensor mode is active) is just an additional
measurement without any effect to the controller
Process control Value
see 4.8.1 Controller
Sensor 2:
sensor TC2 is used for Control. Sensor TC1 (If
both sensor mode is active) is just an additional
measurement without any effect to the controller
Process control Value
see 4.8.1 Controller
One sensor below
The lower value of the TC1 and TC2 sensors is
used for control
only in availed sensor mode both sensors
Process control Value
see 4.8.1 Controller
Both sensors below
The higher value of the TC1 and TC2 sensors is
used for control
only in availed sensor mode both sensors
Process control Value
see 4.8.1 Controller
Soft Limiter
Sensor TC1 is used for Control.
Sensor TC2 is used as an software based limiter.
See 4.8.3 Soft limiter
only in availed sensor mode both sensors
see 4.8.3 Soft limiter
Use of the Soft Limiter function as a limiter is not permitted for
ATEX
and
IECEx
applications
according
to
IEC/IEEE 60079-30-1.
Explosion protection is not ensured by this function.
Use hardware limiter of ESTM-L (SIL II) as limiter for ATEX
and IECEx applications according to IEC/IEEE 60079-30-1.
Temperature Unit
Function
Description
action / - effects on
°C / °F
Switch to the other SI unit (all values are
converted to the respective unit)