Overview of all active alarms and warnings
When
troubleshooting,
the
supplied
OPERATING
INSTRUCTIONS, the safety instructions contained there
in and the generally applicable safety rules must be
observed.
List of Alarm and status massages
ALARM TEXT
Information / trouble shooting
Manual reference
Coding element fault high
Incorrectly connected, defective or missing coding element
Check the Coding element
Coding element fault low
Incorrectly connected, defective or missing coding element
Check the Coding element
Internal hardware fault
Internal
hardware
fault
flowed
by
an
bit
please contact your Local BARTEC represented.
Internal power circuit hotspot 125°C
To prevent a high temperature breakdown in case of a
malfunction (temperature at load power circuit higher the
125°C) the device will override the controller relays and force
switching off. This is a self-protection-function of the device. It
should prevent the irreparable blow of the temperature fuse,
that is placed at the internal hotspot.
Internal power circuit hotspot 135°C
To prevent a high temperature breakdown in case of a
malfunction (temperature at load power circuit higher the
135°C) the device will override the limiter and force trip. This
is a self-protection-function of the Device. It should prevent the
irreparable blow of the internal temperature fuse, that is placed
at the internal hotspot.
Limiter reset condition
Limiter tripped
Max alarm leakage current
see 4.8.4 Heating/Power
information
Max alarm load current
see 4.8.4 Heating/Power
information
Max alarm sensor 1
Max alarm sensor 2
Min alarm load current
see 4.8.4 Heating/Power
information
Pre alarm load current min
see 4.8.4 Heating/Power
information
Min alarm sensor 1
Min alarm sensor 2
Pre alarm leakage current
see 4.8.4 Heating/Power
information
Pre alarm limiter high
Pre alarm sensor 1 min
Pre alarm sensor 2 min
Sensor 1 fault high
The measured value of the temperature sensor is out of valid
range. This could be due to the following reasons:
Sensor not connected
Sensor incorrectly connected
Incorrect sensor type used
wire break
Sensor 1 fault low
Sensor 2 fault high