SureCross™ DX80 Web Configurator
Instruction Manual
RF Devices Tab
Remote Type
Description
Coil (output)
1xxxx - Other slave devices, write only, 1 bit
Discrete Input
3xxxx - Other slave devices, read only, 1 bit
Input Register
3xxxx - SureCross™ slave devices, read only, 16 bit
Holding Register
4xxxx - SureCross slave devices, read/write, 16 bit
Banner Engineering’s SureCross™ slave devices use only input registers and holding registers.
When using slave devices from other manufacturers, please refer to the manufacturer’s
documentation to determine what I/O types they use.
Selecting
None
for remote type negates the rule though it remains in the list until deleted. Unused
rules at the end of the list always show
None
as the remote type.
Slave ID: Enter the slave ID of the device the master is trying to communicate with.
Other Commands
Get button: Reads the master table entries on the Gateway.
Refresh button: Updates the Web Configurator screen with the latest data and status information.
Reset button: If a failure occurs while the data is transmitted to the Gateway device click the Reset
button to reset the error condition.
Node 1
Registers 17-32
Node 2
Registers 33-48
Node 3
Registers 49-64
Master Device
DX80 Gateway
Registers 1-16
Node 1
Registers 17-32
Node 2
Registers 33-48
DX80 Gateway
Registers 1-16
Slave ID 5
Slave ID 2
DX85 Extended Remote I/O
Registers 1-16
DX83 Ethernet Bridge
This sample network shows a DX80
Gateway as the Modbus RTU Master
device. Once the Gateway is set as
the master, communication is ignored
between the Ethernet Bridge (normally
the master) and the Gateway.