Technical data
42
Automation Panel 5000 User's manual V2.11
4.1.4 Environmental properties
4.1.4.1 Temperature specifications
Because it is possible to combine different panels and link modules, the following table provides a component-de-
pendent overview of the maximum ambient temperatures resulting from these combinations.
Information:
The maximum specified ambient temperatures for operation were determined under worst-case con-
ditions. Experience has shown that higher ambient temperatures can be achieved with typical appli-
cations in Microsoft Windows, for example. The relevant test and assessment must be carried out in-
dividually by the user on site (reading out the temperatures in BIOS or using the B&R Control Center,
for example).
Information about worst-case conditions
•
Thermal Analysis Tool (TAT) from Intel for simulating processor load (100% CPU, 100% memory, 100%
graphic)
•
BurnInTest 7.1 from PassMark Software for simulating 100% interface utilization using loopback adapters
(100% Network)
•
2x 1 A USB load
•
Maximum expansion and power consumption of the system
•
100% display brightness
4.1.4.1.1 Maximum ambient temperature for worst-case operation
The table refers to using the panels with a swing arm mounting unit (5ACCMA00.000x-000) or IP54 VESA mounting
unit (5ACCMA00.010x-000).
All temperature specifications in degrees Celsius
(°C) at 500 m above sea level,
non-condensing
Link module
The maximum ambient temperature is typically derated
1°C per 1000 meters starting at 500 m above sea level.
5DLSDL.1001-00
SDL/DVI
5DLSD3.1001-00
SDL3
5DLSD4.1001-00
SDL4
Maximum ambient temperature
55
55
1)
55
5AP5120.1505-000
✓
✓
✓
5AP5130.156B-000
✓
50
50
5AP5130.156C-000
✓
50
50
5AP5230.156B-000
✓
50
50
5AP5230.156C-000
✓
50
50
5AP5130.185B-000
50
50
50
5AP5130.185C-000
✓
50
50
5AP5230.185B-000
✓
50
50
5AP5230.185C-000
✓
50
50
5AP5120.1906-000
✓
50
50
5AP5130.215C-000
50
50
50
5AP5230.215C-000
✓
50
50
5AP5230.215I-000
50
45
45
5AP5130.240C-000
45
45
45
Panels
5AP5230.240C-000
50
45
45
5ACCKP01.xxxx-000
✓
✓
✓
5ACCKP03.xxxx-000
✓
✓
✓
5ACCKP04.xxxx-000
✓
✓
✓
Expansion units
5ACCKP05.xxxx-000
✓
✓
✓
1)
The maximum ambient temperature for SDL3 link module 5DLSD3.1001-00 < Rev. A5 with the corresponding panel is reduced by 5°C.