Installation and wiring
154
Automation Panel 5000 User's manual V2.11
5.5.5 Installing the swing arm mounting unit
The mounting unit can be rotated 180°, which makes it possible to install on a swing arm system from above or
below.
The following requirements must be met:
•
All connected cables must be disconnected.
•
The Automation Panel must no longer be installed on the VESA or swing arm system.
1. Disconnect the power supply cable to the Automation Panel (disconnect the power cable!). Disconnect from
all sources and poles!
2. Carry out electrostatic discharge at the ground connection.
3. Place the Automation Panel on a clean, flat surface.
4. Place the mounting unit on the panel. The openings in the mounting unit must be lined up with the mounting
pins on the panel.
5. Install the mounting unit on the panel using the 8 provided Torx screws (T25: 2x M5x65, 6x M5x12). The
tightening torque for each is 2.5 Nm.
Caution!
Loss of impermeability
•
The gasket must be inspected before installation or reinstallation and at regular intervals
according to the requirements of the operating environment.
•
Replace the entire device if inspection reveals visible scratches, cracks, dirt deposits or
excessive wear.
•
Do not stretch the gasket unnecessarily.
•
Avoid contact between the gasket and the corners and edges of the frame.
•
It is important to ensure that the gasket is completely inserted into the installation notch.
•
The housing components must be secured using the specified tightening torque.
Failure to follow these instructions can result in damage to property.