152
english
7
System functions (continued)
Name
PD
Object
ID
Position
Bit
Length
Data
Type
Description / Contains info
PD Envelope X
Band 4
0xA037
Byte 1
8
UINT8 Mantissa of the calculated vibration RMS in Band 4 of envelope
spectrum analysis for X-axis. The unit is g.
PD Envelope X
Band 5
Byte 2
8
UINT8 Mantissa of the calculated vibration RMS in Band 5 of envelope
spectrum analysis for X-axis. The unit is g.
PD Envelope X
Band 6
Byte 3
8
UINT8 Mantissa of the calculated vibration RMS in Band 6 of envelope
spectrum analysis for X-axis. The unit is g.
PD Envelope
Scaler X 4 – 6
Byte 4
8
INT8
Exponent of the calculated vibration RMS in Bands of envelope
spectrum analysis for X-axis. Scientific notation is used to
represent the calculated values.
The scaler value is recalculated every time when the process
data is updated. The scaler value is adjusted to the biggest
calculated vibration RMS value of Band 4 – 6 value for X-axis.
Example:
Calc. vibr. RMS in Band 1 for X-axis = PD Envelope X
Band 1×10
PDEnv.ScalerX
PD Envelope Y
Band 1
0xA038
Byte 1
8
UINT8 Mantissa of the calculated vibration RMS in Band 1 of envelope
spectrum analysis for Y-axis. The unit is g.
PD Envelope Y
Band 2
Byte 2
8
UINT8 Mantissa of the calculated vibration RMS in Band 2 of envelope
spectrum analysis for Y-axis. The unit is g.
PD Envelope Y
Band 3
Byte 3
8
UINT8 Mantissa of the calculated vibration RMS in Band 3 of envelope
spectrum analysis for Y-axis. The unit is g.
PD Envelope
Scaler Y 1 – 3
Byte 4
8
INT8
Exponent of the calculated vibration RMS in Bands of envelope
spectrum analysis for Y-axis. Scientific notation is used to
represent the calculated values.
The scaler value is recalculated every time when the process
data is updated. The scaler value is adjusted to the biggest
calculated vibration RMS value of Band 1 – 3 value for Y-axis.
Example:
Calc. vibr. RMS in Band 4 for Y-axis = PD Envelope Y
Band 1×10
PDEnv.ScalerY
PD Envelope Y
Band 4
0xA039
Byte 1
8
UINT8 Mantissa of the calculated vibration RMS in Band 4 of envelope
spectrum analysis for Y-axis. The unit is g.
PD Envelope Y
Band 5
Byte 2
8
UINT8 Mantissa of the calculated vibration RMS in Band 5 of envelope
spectrum analysis for Y-axis. The unit is g.
PD Envelope Y
Band 6
Byte 3
8
UINT8 Mantissa of the calculated vibration RMS in Band 6 of envelope
spectrum analysis for Y-axis. The unit is g.
PD Envelope
Scaler Y 4 – 6
Byte 4
8
INT8
Exponent of the calculated vibration RMS in Bands of envelope
spectrum analysis for Y-axis. Scientific notation is used to
represent the calculated values.
The scaler value is recalculated every time when the process
data is updated. The scaler value is adjusted to the biggest
calculated vibration RMS value of Band 4 – 6 value for Y-axis.
Example:
Calc. vibr. RMS in Band 4 for Y-axis = PD Envelope Y
Band 1×10
PDEnv.ScalerY
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor