www.balluff.com
131
english
7.2
Diagnosis Suppression
7.2.1 Description
Diagnosis suppression is used to suppress diagnosis
messages from the device. There are two possibilities here:
– Diagnosis Level Configuration that permits a general
suppression of messages of a certain level (message,
warning, error).
– Event-code suppression of up to 5 events as a list or
via teach-in.
7.2.2 ISDU
Name
Index
Subindex Access Length
Data Type
Data Storage Default
Diagnosis Level Configuration
0x0070 (112)
0
R/W
1 byte
UINT8(ENUM)
Yes
0
Event Code Suppression
0x0071 (113)
0
R/W
10 bytes
–
Yes
–
Event Code Suppression
1…5
R/W
2 bytes
UINT16
No
0
Event Code Suppression
Teach-in
0x0072 (114)
0
W
2 bytes
UINT16
n/a
–
Event Code Suppression
Delete
0x0073 (115)
0
W
2 bytes
UINT16
n/a
–
Tab. 7-5: Diagnosis Suppression – ISDU
7.2.3 Diagnosis Level Configuration
This parameter offers the possibility to select an output
level for events.
This index is part of the data management and is stored in
non-volatile memory.
Value
Diagnosis Level
Descriptions
0
All events
All diagnosis messages are reported (default setting).
1
Warnings and errors
All warnings and errors are reported – messages are suppressed.
2
Error
Only events of type error are reported.
3
No events
All diagnosis messages from the device are suppressed.
Tab. 7-6: Diagnosis Suppression – Diagnosis Level Configuration
7
System functions (continued)
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor
Содержание BCM R16E-004-CI01-S4 Series
Страница 2: ...www balluff com...
Страница 3: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Konfigurationsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 165: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Configuration guide english...
Страница 166: ...www balluff com...