www.balluff.com
41
english
3
Overview of IO-Link data and functions (continued)
3.5
Events
Event Code Event Type
Event – Description – Remedy
Device Status
0x1850
(6224)
Notification
Process data profile selection cannot be used –
default value is used.
0 – Device is operating properly.
0x1851
(6225)
Notification
Process Data Update Timeout
– For information
purposes only.
0 – Device is operating properly.
0x1852
(6226)
Warning
Multiple
Process Data Update Timeout
– For
information purposes only.
0 – Device is operating properly.
0x4000
(16384)
Error
Temperature Fault – Overload
– The device is
operated outside of the device-specific temperature
limits. Risk of device damage.
4 – Failure
0x4210
(16912)
Warning
Device Temperature Overrun – Clear Heat Of Source
– Risk of device damage. The device is too hot.
►
Remove heat source, provide the device with
heat insulation if necessary.
2 – Out-of-Specification
0x4220
(16928)
Warning
Device Temperature Underrun – Insulate Device
–
Risk of device damage. The device is too cold.
►
Insulate the device.
2 – Out-of-Specification
0x5110
(20752)
Warning
Primary supply voltage exceeded
►
Check for deviations in the supply.
2 – Out-of-Specification
0x5111
(20753)
Warning
Primary supply voltage below minimum value
►
Check for deviations in the supply.
2 – Out-of-Specification
0x8CD0
(36048)
Warning
Inclination alarm
►
Check installation.
1 – Maintenance-Required
0x8D0A
(36106)
ERROR
Short circuit on Pin 4
►
Check installation.
4 – Failure
0x8D0B
(36107)
ERROR
Overload or short circuit at pin 2
►
Check wiring.
►
Check installation.
4 – Failure
0x8D10
(36112)
Warning
Device Temperature Upper Warning
– The set upper
temperature warning threshold has been exceeded.
0 – Device is operating properly.
0x8D18
(36120)
Notification
One of the Switching Counter channels reached its
set limit.
►
Check
Switching Counter
.
0 – Device is operating properly.
0x8D19
(36121)
Warning
One of the Switching Counter channels reached the
maximum counter value.
►
Check
Switching Counter
.
0 – Device is operating properly.
0x8D20
(36128)
Warning
Device Temperature Lower Warning
– The set lower
temperature warning threshold is below the minimum
value.
0 – Device is operating properly.
0x8D24
(36132)
Warning
Parameter write error – for information purposes
only.
0 – Device is operating properly.
0x8D25
(36133)
Error
Parameters not consistent – basic settings are used,
service required. Parameterization processes and
resets can no longer be performed.
4 – Failure
0x8D26
(36134)
Warning
User data was reset to the default settings.
►
Check settings and acknowledge warning.
1 - Maintenance required
Tab. 3-3: Events – Overview
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor