Primary device functions (continued)
Object
ID
Name
Description
Direction
0xA049
Severity Zone
C
1 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M is
between Severity Zone Boundary B/C and Severity Zone Boundary C/D for at least
Alarm Set Delay ms.
0 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M is
out of the range defined by Severity Zone Boundary B/C and Severity Zone
Boundary C/D for at least Alarm Set Delay ms.
Input
0xA04A
Severity Zone
D
1 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M
exceeds Severity Zone Boundary C/D for at least Alarm Set Delay ms.
0 – If the largest value of PD v-RMS X, PD v-RMS Y, PD v-RMS Z, PD v-RMS M
doesn't exceed Severity Zone Boundary C/D for at least Alarm Set Delay ms.
Input
0xA06C
PD Pre-Alarm
v-RMS X
1 – If PD v-RMS X ≥ Pre-Alarm Level v-RMS X for at least Alarm Set Delay ms.
0 – If PD v-RMS X < Pre-Alarm Level v-RMS X for at least Alarm Reset Delay ms.
Input
0xA06D
PD Pre-Alarm
v-RMS Y
1 – If PD v-RMS Y ≥ Pre-Alarm Level v-RMS Y for at least Alarm Set Delay ms.
0 – If PD v-RMS Y < Pre-Alarm Level v-RMS Y for at least Alarm Reset Delay ms.
Input
0xA06E
PD Pre-Alarm
v-RMS Z
1 – If PD v-RMS Z ≥ Pre-Alarm Level v-RMS Z for at least Alarm Set Delay ms.
0 – If PD v-RMS Z < Pre-Alarm Level v-RMS Z for at least Alarm Reset Delay ms.
Input
0xA06F
PD Pre-Alarm
v-RMS M
1 – If PD v-RMS M ≥ Pre-Alarm Level v-RMS M for at least Alarm Set Delay ms.
0 – If PD v-RMS M < Pre-Alarm Level v-RMS M for at least Alarm Reset Delay ms.
Input
0xA070
PD Main-Alarm
v-RMS X
1 – If PD v-RMS X ≥ Main-Alarm Level v-RMS X for at least Alarm Set Delay ms.
0 – If PD v-RMS X < Main-Alarm Level v-RMS X for at least Alarm Reset Delay ms.
Input
0xA071
PD Main-Alarm
v-RMS Y
1 – If PD v-RMS Y ≥ Main-Alarm Level v-RMS Y for at least Alarm Set Delay ms.
0 – If PD v-RMS Y < Main-Alarm Level v-RMS Y for at least Alarm Reset Delay ms.
Input
0xA072
PD Main-Alarm
v-RMS Z
1 – If PD v-RMS Z ≥ Main-Alarm Level v-RMS Z for at least Alarm Set Delay ms.
0 – If PD v-RMS Z < Main-Alarm Level v-RMS Z for at least Alarm Reset Delay ms.
Input
0xA073
PD Main-Alarm
v-RMS M
1 – If PD v-RMS M ≥ Main-Alarm Level v-RMS M for at least Alarm Set Delay ms.
0 – If PD v-RMS M < Main-Alarm Level v-RMS M for at least Alarm Reset
Delay ms.
Input
0xA074
PD Pre-Alarm
v-Peak X
1 – If PD v-Peak X ≥ Pre-Alarm Level v-Peak X for at least Alarm Set Delay ms.
0 – If PD v-Peak X < Pre-Alarm Level v-Peak X for at least Alarm Reset Delay ms.
Input
0xA075
PD Pre-Alarm
v-Peak Y
1 – If PD v-Peak Y ≥ Pre-Alarm Level v-Peak Y for at least Alarm Set Delay ms.
0 – If PD v-Peak Y < Pre-Alarm Level v-Peak Y for at least Alarm Reset Delay ms.
Input
0xA076
PD Pre-Alarm
v-Peak Z
1 – If PD v-Peak Z ≥ Pre-Alarm Level v-Peak Z for at least Alarm Set Delay ms.
0 – If PD v-Peak Z < Pre-Alarm Level v-Peak Z for at least Alarm Reset Delay ms.
Input
0xA077
PD Pre-Alarm
v-Peak M
1 – If PD v-Peak M ≥ Pre-Alarm Level v-Peak M for at least Alarm Set Delay ms.
0 – If PD v-Peak M < Pre-Alarm Level v-Peak M for at least Alarm Reset Delay ms.
Input
0xA078
PD Main-Alarm
v-Peak X
1 – If PD v-Peak X ≥ Main-Alarm Level v-Peak X for at least Alarm Set Delay ms.
0 – If PD v-Peak X < Main-Alarm Level v-Peak X for at least Alarm Reset Delay ms.
Input
0xA079
PD Main-Alarm
v-Peak Y
1 – If PD v-Peak Y ≥ Main-Alarm Level v-Peak Y for at least Alarm Set Delay ms.
0 – If PD v-Peak Y < Main-Alarm Level v-Peak Y for at least Alarm Reset Delay ms.
Input
0xA07A PD Main-Alarm
v-Peak Z
1 – If PD v-Peak Z ≥ Main-Alarm Level v-Peak Z for at least Alarm Set Delay ms.
0 – If PD v-Peak Z < Main-Alarm Level v-Peak Z for at least Alarm Reset Delay ms.
Input
0xA07B PD Main-Alarm
v-Peak M
1 – If PD v-Peak M ≥ Main-Alarm Level v-Peak M for at least Alarm Set Delay ms.
0 – If PD v-Peak M < Main-Alarm Level v-Peak M for at least Alarm Reset
Delay ms.
Input
0xA07C
PD Pre-Alarm
a-RMS X
1 – If PD a-RMS X ≥ Pre-Alarm Level a-RMS X for at least Alarm Set Delay ms.
0 – If PD a-RMS X < Pre-Alarm Level a-RMS X for at least Alarm Reset Delay ms.
Input
0xA07D
PD Pre-Alarm
a-RMS Y
1 – If PD a-RMS Y ≥ Pre-Alarm Level a-RMS Y for at least Alarm Set Delay ms.
0 – If PD a-RMS Y < Pre-Alarm Level a-RMS Y for at least Alarm Reset Delay ms.
Input
0xA07E
PD Pre-Alarm
a-RMS Z
1 – If PD a-RMS Z ≥ Pre-Alarm Level a-RMS Z for at least Alarm Set Delay ms.
0 – If PD a-RMS Z < Pre-Alarm Level a-RMS Z for at least Alarm Reset Delay ms.
Input
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor
Содержание BCM R16E-004-CI01-S4 Series
Страница 2: ...www balluff com...
Страница 3: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Konfigurationsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 165: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Configuration guide english...
Страница 166: ...www balluff com...