Primary device functions (continued)
PD
Object ID
Name
Bit
Length
Data
Type
Description / Contains info
0XA04F
PD Alarm
Band 5
1
BOOL Cumulative flag of PD Alarm X Band 5, PD Alarm Y Band 5, PD Alarm Z
Band 5
based on the values of
Enable Alarms X
,
Enable Alarms Y
,
Enable Alarms Z
.
1 – If
(PD Alarm X Band 5 AND Enable Alarms X is set) OR
(PD Alarm Y Band 5 AND Enable Alarms Y is set) OR
(PD Alarm Z Band 5 AND Enable Alarms Z is set)
0 – If
(PD Alarm X Band 5 OR Enable Alarms X is cleared) AND
(PD Alarm Y Band 5 OR Enable Alarms Y is cleared) AND
(PD Alarm Z Band 5 OR Enable Alarms Z is cleared)
0XA050
PD Alarm
Band 6
1
BOOL Cumulative flag of PD Alarm X Band 6, PD Alarm Y Band 6, PD Alarm Z
Band 6
based on the values of
Enable Alarms X
,
Enable Alarms Y
,
Enable Alarms Z
.
1 – If
(PD Alarm X Band 6 AND Enable Alarms X is set) OR
(PD Alarm Y Band 6 AND Enable Alarms Y is set) OR
(PD Alarm Z Band 6 AND Enable Alarms Z is set)
0 – If
(PD Alarm X Band 6 OR Enable Alarms X is cleared) AND
(PD Alarm Y Band 6 OR Enable Alarms Y is cleared) AND
(PD Alarm Z Band 6 OR Enable Alarms Z is cleared)
0XA051
System
Error
1
BOOL 1 – If the filter settling time of
Frequency Domain Analysis
is not finished
after startup/reconfiguration OR the first (since startup or reconfiguration)
FFT calculation of the
Frequency Domain Analysis
is not finished.
0 – If the filter settling time of Frequency Domain Analysis is finished AND
the first FFT calculation of the Frequency Domain Analysis is finished.
The value of this Status bit can be set by other features (e. g.
Time Domain
Analysis
). The logical relation between these different set sources is OR.
0XA054
PD Alarm X
Band 1
1
BOOL 1 – If the calc. vibr. RMS in Band 1 for X-axis ≥
Alarm Level Band 1 X
for at
least
Alarm Set Delay ms
.
0 – If the calc. vibr. RMS in Band 1 for X-axis <
Alarm Level Band 1 X
for at
least
Alarm Reset Delay ms
.
0XA055
PD Alarm X
Band 2
1
BOOL 1 – If the calc. vibr. RMS in Band 2 for X-axis ≥
Alarm Level Band 2 X
for at
least
Alarm Set Delay ms
.
0 – If the calc. vibr. RMS in Band 2 for X-axis <
Alarm Level Band 2 X
for at
least
Alarm Reset Delay ms
.
0XA056
PD Alarm X
Band 3
1
BOOL 1 – If the calc. vibr. RMS in Band 3 for X-axis ≥
Alarm Level Band 3 X
for at
least
Alarm Set Delay ms
.
0 – If the calc. vibr. RMS in Band 3 for X-axis <
Alarm Level Band 3 X
for at
least
Alarm Reset Delay ms
.
0XA057
PD Alarm X
Band 4
1
BOOL 1 – If the calc. vibr. RMS in Band 4 for X-axis ≥
Alarm Level Band 4 X
for at
least
Alarm Set Delay ms
.
0 – If the calc. vibr. RMS in Band 4 for X-axis <
Alarm Level Band 4 X
for at
least
Alarm Reset Delay ms
.
0XA058
PD Alarm X
Band 5
1
BOOL 1 – If the calc. vibr. RMS in Band 5 for X-axis ≥
Alarm Level Band 5 X
for at
least
Alarm Set Delay ms
.
0 – If the calc. vibr. RMS in Band 5 for X-axis <
Alarm Level Band 5 X
for at
least
Alarm Reset Delay ms
.
0XA059
PD Alarm X
Band 6
1
BOOL 1 – If the calc. vibr. RMS in Band 6 for X-axis ≥
Alarm Level Band 6 X
for at
least
Alarm Set Delay ms
.
0 – If the calc. vibr. RMS in Band 6 for X-axis <
Alarm Level Band 6 X
for at
least
Alarm Reset Delay ms
.
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor