www.balluff.com
147
english
7.10.2 Available PDObjects
Various parameters (PDObjects) are available in different
data types, which can be placed in slots.
1× FLOAT32 PDObjects
PD
Object ID
Name
Direction
Direction
0xA009
PD v-RMS X
Determines the calculated velocity RMS of X-axis. The unit is mm/s.
Input
0xA00A
PD v-RMS Y
Determines the calculated velocity RMS of Y-axis. The unit is mm/s.
Input
0xA00B
PD v-RMS Z
Determines the calculated velocity RMS of Z-axis. The unit is mm/s.
Input
0xA00C
PD v-RMS M
Determines the calculated velocity RMS of magnitude. The unit is mm/s.
Input
0xA00D
PD v-Peak X
Determines the calculated velocity Peak of X-axis. The unit is mm/s.
Input
0xA00E
PD v-Peak Y
Determines the calculated velocity Peak of Y-axis. The unit is mm/s.
Input
0xA00F
PD v-Peak Z
Determines the calculated velocity Peak of Z-axis. The unit is mm/s.
Input
0xA010
PD v-Peak M
Determines the calculated velocity Peak of magnitude. The unit is mm/s.
Input
0xA001
PD a-RMS X
Determines the calculated acceleration RMS of X-axis. The unit is g.
Input
0xA002
PD a-RMS Y
Determines the calculated acceleration RMS of Y-axis. The unit is g.
Input
0xA003
PD a-RMS Z
Determines the calculated acceleration RMS of Z-axis. The unit is g.
Input
0xA004
PD a-RMS M
Determines the calculated acceleration RMS of magnitude. The unit is g.
Input
0xA005
PD a-Peak X
Determines the calculated acceleration Peak of X-axis. The unit is g.
Input
0xA006
PD a-Peak Y
Determines the calculated acceleration Peak of Y-axis. The unit is g.
Input
0xA007
PD a-Peak Z
Determines the calculated acceleration Peak of Z-axis. The unit is g.
Input
0xA008
PD a-Peak M
Determines the calculated acceleration Peak of magnitude. The unit is g.
Input
0xA011
PD a-Crest X
Determines the calculated acceleration Crest Factor of X-axis. Without unit.
Input
0xA012
PD a-Crest Y
Determines the calculated acceleration Crest Factor of Y-axis. Without unit.
Input
0xA013
PD a-Crest Z
Determines the calculated acceleration Crest Factor of Z-axis. Without unit.
Input
0xA014
PD a-Crest M
Determines the calculated acceleration Crest Factor of magnitude.
Without unit.
Input
0xA015
PD a-Kurtosis X
1)
Determines the calculated acceleration Kurtosis of X-axis. Without unit.
Input
0xA016
PD a-Kurtosis Y
1)
Determines the calculated acceleration Kurtosis of Y-axis. Without unit.
Input
0xA017
PD a-Kurtosis M
1)
Determines the calculated acceleration Kurtosis of Z-axis. Without unit.
Input
0xA018
PD a-Skewness X
1)
Determines the calculated acceleration Skewness of X-axis. Without unit.
Input
0xA019
PD a-Skewness Y
1)
Determines the calculated acceleration Skewness of Y-axis. Without unit.
Input
0xA01A
PD a-Skewness M
1)
Determines the calculated acceleration Skewness of Z-axis. Without unit.
Input
1)
only for BCM R16E-004-CI02-_ _ , _-S4
Tab. 7-29: 1× FLOAT32 PDObjects
1× UINT16 PDObjects
PD
Object ID
Name
Data
Type
Bit
Length
Description / Contains Info
0xA0E0
PD RPM used
UINT16
16
The used RPM value
Tab. 7-30: 1× UINT16 PDObjects
7
System functions (continued)
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor
Содержание BCM R16E-004-CI01-S4 Series
Страница 2: ...www balluff com...
Страница 3: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Konfigurationsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 165: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Configuration guide english...
Страница 166: ...www balluff com...