54
english
5
Primary device functions (continued)
Name
Index
Sub-
index
Access
Length
Data
Type
Data
Storage
Default
Vibration Acceleration Peak Alarm
Configuration
0x2167
(8551)
0
RW
36 bytes
ArrayT
Yes
–
Pre-Alarm Level a-Peak X
1
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Main-Alarm Level a-Peak X
2
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Pre-Alarm Level a-Peak Y
3
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Main-Alarm Level a-Peak Y
4
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Pre-Alarm Level a-Peak Z
5
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Main-Alarm Level a-Peak Z
6
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Pre-Alarm Level a-Peak M
7
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Main-Alarm Level a-Peak M
8
RW
4 bytes
FLOAT32
No
16
Min.: 0, Max.: 16
Enable Alarm Level a-Peak X
9
RW
1 byte
BOOL
No
False
Min.: 0, Max.: 255
Enable Alarm Level a-Peak Y
0A
RW
1 byte
BOOL
No
False
Min.: 0, Max.: 255
Enable Alarm Level a-Peak Z
0B
RW
1 byte
BOOL
No
False
Min.: 0, Max.: 255
Enable Alarm Level a-Peak M
0C
RW
1 byte
BOOL
No
False
Min.: 0, Max.: 255
BCM R16E-004-CI0 _ - _ _ , _-S4
Condition Monitoring Sensor
Содержание BCM R16E-004-CI01-S4 Series
Страница 2: ...www balluff com...
Страница 3: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Konfigurationsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 165: ...BCM R16E 004 CI01 _ _ _ S4 BCM R16E 004 CI02 _ _ _ S4 Configuration guide english...
Страница 166: ...www balluff com...