7-26
VS1MD AC Drive User Manual
t63
Frequency Loss Wait Time
Range:
0.1-120 [sec]
Default:
1.0
Access
Tunable
See Also:
P40, t35, t62
This is the time delay before the drive takes action in the event of a
command frequency loss. If there is no frequency command input during
the time set in this parameter, the drive starts to operate in the mode
selected in t62.
t64
Communication Time Setting
Range:
2-100 [ms]
Default:
5
Access
Tunable
See Also:
t59-t61, t65-t81
Frame Communication time.
t65
Parity/Stop Bit Setting
Range:
0=Parity: None, Stop Bit: 1
1=Parity: None, Stop Bit: 2
2=Parity: Even, Stop Bit: 1
3=Parity: Odd, Stop Bit: 1
Default:
0
Access
Tunable
See Also:
t59-t61, t64, t66-t81
When the protocol is set, the communication format can be set.
t66
Read address register 1
t67
Read address register 2
t68
Read address register 3
t69
Read address register 4
t70
Read address register 5
t71
Read address register 6
t72
Read address register 7
t73
Read address register 8
Range:
0-42239
Default:
t66=5, t67=6, t68=7, t69=8, t70=9, t71=10, t72=11, t73=12
Access
Tunable
The user can register up to 8 discontinuous addresses and read them all
with one read command.
Содержание VS1MD
Страница 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Страница 5: ...4 VS1MD AC Drive User Manual...
Страница 11: ...1 2 VS1MD AC Drive User Manual...
Страница 27: ...4 8 VS1MD AC Drive User Manual...
Страница 103: ...7 58 VS1MD AC Drive User Manual...
Страница 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Страница 133: ...8 30 VS1 MD AC Drive User Manual...
Страница 143: ...9 10 VS1 MD AC Drive User Manual...
Страница 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Страница 155: ...B 10 VS1MD User Manual...
Страница 167: ...VS1MD User Manual...
Страница 168: ......
Страница 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...