8-8
VS1-MD AC Drive User Manual
Motor runs in Reverse direction when input voltage to V1-CM is between 0 and 10[V]
and REV RUN command is active. When input voltage polarity is reversed to –10 to
0[V], motor decelerates to stop and runs in forward direction.
8.2
UP-Down
Up/down Save function: If F63, ‘Save up/down frequency’, is set to 1, the frequency
before the inverter was stopped or decelerated is saved in F64
.
The Up/down frequency can be initialized by setting the multi-function input terminal
as ‘Up/Down Save Frequency Initialization’.
Group
Display
Parameter Name
Setting
Range
Default
Unit
I/O
group
t1
[Multi-function Input Terminal P1 Selection]
0
0 to 25
0
to
to
t7
[Multi-function Input Terminal P7 Selection]
15
6
t8
[Multi-function Input Terminal P8 Selection]
16
7
Select terminals for Up-Down operation from P1-P8.
If P7 and P8 are selected, set t7 and t8 to 15 [Frequency Up command] and 16 [Frequency Down
command], respectively.
If P6 is selected, set t6 to t8 [Up/Down Save Frequency Initialization].
F63
Save up/down frequency select
0
Remove ‘save up/down frequency’
1
Set ‘save up/down frequency’
F64
Save up/down frequency
Up/down frequency saved
3
3
3
,
,
&0
,
3 ,
t1
t6
t7
t8
P7 (UP)
P8 (DOWN)
Frequency
Run
command(FX)
Содержание VS1MD
Страница 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Страница 5: ...4 VS1MD AC Drive User Manual...
Страница 11: ...1 2 VS1MD AC Drive User Manual...
Страница 27: ...4 8 VS1MD AC Drive User Manual...
Страница 103: ...7 58 VS1MD AC Drive User Manual...
Страница 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Страница 133: ...8 30 VS1 MD AC Drive User Manual...
Страница 143: ...9 10 VS1 MD AC Drive User Manual...
Страница 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Страница 155: ...B 10 VS1MD User Manual...
Страница 167: ...VS1MD User Manual...
Страница 168: ......
Страница 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...