7-32
VS1MD AC Drive User Manual
F28
Torque boost in forward direction
F29
Torque boost in reverse direction
Range:
0-15 [%]
Default:
2
Access
Configurable
See Also:
F27-F29
This parameter sets the amount of torque boost applied to a motor during
forward or reverse run. It is set as a percent of maximum output voltage.
F30
V/F Pattern
Range:
0=Linear
1=Square
2=User V/F
Default:
0
Access
Configurable
See Also:
P34, P35, F31-F38, H40
Selects a pattern for the drive.
0 = Linear volts per hertz ratio from P35 – Frequency low limit to P34 –
Base frequency.
1 = Squared volts per hertz ratio. Applications are fans, pumps or variable
torque.
Run
command
Freq.
Start freq.
Base freq.
Voltage
Inverter rated
voltage
Freq.
Base freq.
100%
Voltage
Содержание VS1MD