Parameter Descriptions
7-31
F14
Time for magnetizing a motor
Range:
0-60 [sec]
Default:
0.1
Access
Configurable
See Also:
P30, P32, H32, H34, H40, H42, H44
This parameter accelerates the motor after pre-exciting the motor for the set
time. The amount of the pre-exciting current is set in H34 – Motor no load
current.
F20
Jog Frequency
Range:
0-400 [Hz]
Default:
10.00
Access
Tunable
See Also:
P36, t1-t8
This parameter sets the Jog Frequency, it cannot be set above P36 –
Frequency High Limit. Jog is only available in 2-wire control mode.
F27
Torque Boost select
Range:
0=Manual Torque Boost
1=Auto Torque Boost
Default:
0
Access
Configurable
See Also:
F28-F29, H34, H41-42
If F27 = 0, set manual torque boost values in F28 and F29.
If F27 = 1 (Auto toque boost), the inverter automatically calculates torque
boost values using motor parameters and outputs the corresponding
voltage. Before enabling Auto torque boost, H34 – No load current and H42
– Stator resistance must be set properly.
FX
Time
RX
Voltage
F28 - FX
torque boost
No torque boost
100%
F29 - RX
torque boost
Содержание VS1MD
Страница 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Страница 5: ...4 VS1MD AC Drive User Manual...
Страница 11: ...1 2 VS1MD AC Drive User Manual...
Страница 27: ...4 8 VS1MD AC Drive User Manual...
Страница 103: ...7 58 VS1MD AC Drive User Manual...
Страница 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Страница 133: ...8 30 VS1 MD AC Drive User Manual...
Страница 143: ...9 10 VS1 MD AC Drive User Manual...
Страница 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Страница 155: ...B 10 VS1MD User Manual...
Страница 167: ...VS1MD User Manual...
Страница 168: ......
Страница 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...