7-54
VS1MD AC Drive User Manual
H75
DB Resistor Select
Range:
0 - 1
Default:
1
Access
Configurable
See Also:
H76
0 = Unlimited
1 = Limited by setting in H76
ATTENTION:
Take caution when DB resistor is used over its Watt rating.
Fire may result from resistor overheat. When resistor having heat detection
sensor is used, sensor output can be used as external trip signal in digital
input.
H76
DB Resistor Operating Rate
Range:
0-30[%]
Default:
10
Access
Configurable
See Also:
H75
Sets the percent of DB resistor operating rate to be activated during one
sequence of operation. Continuous usage rate is a maximum of 15
seconds.
Example 1)
T_acc: Acceleration time to reach a setting freq.
T_steady: Time for constant speed operation at setting freq.
T_dec: Time to decelerate to lower freq. than that in constant speed
or time to stop from freq. in constant speed.
T_stop: waiting time at a stop before operation is resumed.
[%]
100
_
_
_
_
_
76
×
+
+
+
=
stop
T
dec
T
steady
T
acc
T
dec
T
H
)UHT
7BDFF 7BVWHDG\ 7BGHF
7BVWRS
Содержание VS1MD
Страница 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Страница 5: ...4 VS1MD AC Drive User Manual...
Страница 11: ...1 2 VS1MD AC Drive User Manual...
Страница 27: ...4 8 VS1MD AC Drive User Manual...
Страница 103: ...7 58 VS1MD AC Drive User Manual...
Страница 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Страница 133: ...8 30 VS1 MD AC Drive User Manual...
Страница 143: ...9 10 VS1 MD AC Drive User Manual...
Страница 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Страница 155: ...B 10 VS1MD User Manual...
Страница 167: ...VS1MD User Manual...
Страница 168: ......
Страница 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...