7-6
VS1MD AC Drive User Manual
The drive outputs its rated voltage to the motor at this frequency (enter motor
nameplate). See parameter F30 for custom V/Hz settings and V/Hz curve.
Sets drive minimum steady state output frequency.
Sets drive maximum steady state output frequency.
This parameter manually sets the frequency that the drive is commanded to output.
Set the desired frequency and press ENTER/PROG to lock the value into memory. If
the drive is running, it will immediately accelerate or decelerate to this value once
enter is pressed. If the drive is not running, entering a value in P37 will pre-set the
speed to accelerate to after a valid run command.
P34
Base Frequency
Range:
30 - 400 [Hz]
Default:
60
Access
Configurable
See Also:
P30, P33, F30-F38
P35
Frequency Low Limit
Range:
0 - P36 [Hz]
Default:
10.0
Access
Configurable
See Also:
P36, F30-F38
P36
Frequency High Limit
Range:
0 - 400 [Hz]
Default:
60.0
Access
Configurable
See Also:
P35
P37
Frequency Command
Range:
0 - 400 [Hz]
Default:
0.00
Access
Tunable
Содержание VS1MD
Страница 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Страница 5: ...4 VS1MD AC Drive User Manual...
Страница 11: ...1 2 VS1MD AC Drive User Manual...
Страница 27: ...4 8 VS1MD AC Drive User Manual...
Страница 103: ...7 58 VS1MD AC Drive User Manual...
Страница 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Страница 133: ...8 30 VS1 MD AC Drive User Manual...
Страница 143: ...9 10 VS1 MD AC Drive User Manual...
Страница 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Страница 155: ...B 10 VS1MD User Manual...
Страница 167: ...VS1MD User Manual...
Страница 168: ......
Страница 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...