7-56
VS1MD AC Drive User Manual
1 = Operation stops when cooling fan malfunctions
When cooling fan fault occurs,
message is displayed on the
LED and operation is stopped. If t32 and/or t33 is set to 17 (Fault Output),
fault message is displayed.
H81 -
H90
Second Motor Parameters
Range:
See below
Default:
See below
Access
Configurable
See Also:
t1-t8
These parameters activate when a selected terminal is ON and one of the
t1 thru t8 terminals is set for 12 (2
nd
Motor Select).
Use these settings when an inverter operates two motors connected to two
different types of loads. 2
nd
motor operation does not drive two motors at
the same time. When first selected motor operation is stopped, select a
terminal for the second motor and define H81 thru H90 to run the second
motor.
Sets the V/F pattern for the second motor.
Param.
Description
Range
Factory Default
Adj. run
H81
Accel Time
0 ~ 60000 Sec
1.0
H82
Decel Time
0 ~ 60000 Sec
5.0
H83
Base Freq
30 ~ 400 Hz
60.0
-
H84
V/F Pattern
0 ~ 2
0
-
H85
FX Torque Boost
0 ~ 15 %
5
-
H86
RX Torque Boost
0 ~ 15 %
5
-
H87
Stall Level
30 ~ 150 %
150
-
H88
1 Min Overload Level
50 ~ 200 %
150
H89
Continuous Overload Level
50 ~ 150 %
100
H90
Motor Rated Current
0.1 ~ 50 Amps
26.3
-
M 1
M 2
VS1MD
P8
Содержание VS1MD
Страница 2: ...Instruction Manual VS1MD User Manual MN760 3 6 07...
Страница 5: ...4 VS1MD AC Drive User Manual...
Страница 11: ...1 2 VS1MD AC Drive User Manual...
Страница 27: ...4 8 VS1MD AC Drive User Manual...
Страница 103: ...7 58 VS1MD AC Drive User Manual...
Страница 131: ...8 28 VS1 MD AC Drive User Manual 8 13 Control Block Diagram m G k G h Vk Vm w t t...
Страница 133: ...8 30 VS1 MD AC Drive User Manual...
Страница 143: ...9 10 VS1 MD AC Drive User Manual...
Страница 150: ...Options Kits B 5 B 2 4 VS1MD NM1C B 2 5 VS1MD NM1D...
Страница 155: ...B 10 VS1MD User Manual...
Страница 167: ...VS1MD User Manual...
Страница 168: ......
Страница 169: ...Publication MN760 3 2007 Baldor Electric Company All rights reserved...