X. Operating Principles
A. 2900 Series with Type 39PV (Pop) Pilot Operational Descriptions
PV Valve Closed (Normal Position)
System pressure from the main valve inlet is fed to the dome by the pilot through interconnecting tubing. This
equalizes the pressure on the top of the piston with inlet pressure on the seating surface (bottom) of the disc. Since
the area of the top of the piston is larger than the area of the seating surface, the differential area results in a net
downward force keeping the main valve tightly closed.
Figure 8: PV Valve Closed (Normal Position)
Consolidated 2900 Series POSRV Maintenance Manual
|
21