XXII. 2900 Pilot Valve Options (Contd.)
F. Gag
A manual method of locking a pilot operated relief
valve in the closed position for system hydrostatic test.
39MV72 limited to 4800 psig (330.9 barg) with gag option
(Figure 71).
G. Heat Exchanger
This allows the temperature range for the 3900 POSRV
with metal seats to be extended to -320°F to 650°F
(-195.5°C to 343.3°C). Not available above 3750 psig
(258.5 barg). When the heat exchanger is selected, the
POSRV shall be piped so that the media enters the heat
exchanger first to condition the media’s temperature.
Option(s) such as line filter, canister filter, 5-way
manifold valve, pressure differential switch, pressure
spike snubber, etc. shall be piped downstream of the
heat exchanger (Figures 72 & 73).
Figure 72: Heat Exchanger - Hot Service
Figure 73: Heat Exchanger - Cold Service
Figure 71: Gag
Consolidated 2900 Series POSRV Maintenance Manual
|