IIOIC12 HARDWARE
KEYBOARD MODULE REMOVAL
5 - 4
I-E96-107-2N
®
KEYBOARD MODULE REMOVAL
To remove the OIC’s IIMKM01 multibus card, remove the four
nuts that hold the card to the bottom of the CRT mounting plate.
NOTE: Remove all wiring to the card before loosening the nuts.
MULTIBUS KEYBOARD MODULE
•
Elsag Bailey Nomenclature - IIMKM01.
The Multibus Keyboard Interface Module (MKM) interfaces the key-
board and other operator input devices to the OIC12. The MKM is
mounted under the CRT mounting plate. There are four jumpers
on the MKM board to set for proper operation. J1 controls serial
port two (P9). Connecting the eight pins horizontally configures the
serial port as data communication equipment to the default shown
in Figure
. For DCE, data is transmitted from the MKM on pin
three of the connector and received from the connected device on
pin two of the connector. Connecting the eight pins for P9, vertically
configures the serial port as data terminal equipment (DTE). For
DTE, data is transmitted from the MKM on pin two of the connector
and received from the connected device on pin three of the
connector.
CAUTION
Failure to turn off the main power circuit breaker before remov-
ing or inserting modules may result in equipment failure.
Figure 5-3. IIMK01/01A Multibus Keyboard Module
P18
P7
CABLE L700579V19-04
P17
P8
P9
(FUTURE)
J1
P16
GS940106
J3
RIBBON CABLE TO
PEP (ALARM CONTACTS)
6634512_26N72
TO I/O DISTRIBUTION
BOARD
6638712_1 TO
PFI ON POWER SUPPLY
P15
P6
6638849_1
TO ADP AND I/O
DISTRIBUTION BOARD
P14
P5
6638719_1 TO
RESET SWITCH ON PEP
P4
P3
J5
A10
J4