IIOIS12 HARDWARE
MULTIBUS CHASSIS HARDWARE
4 - 10
I-E96-107-2N
®
Table 4-7. Multibus Communication Processor
Configuration - Switch 1
Baud Rates
Po
le
s
1
-4
Po
rt
A
0000 = N/U
0001 = 1800
1000 = 75
1001 = 2000
0100 = 110
0101 = 2400
1100 = 134.5
1101 = N/U
0010 = 150
0011 = 4800
1010 = 300
1011 = N/U
0110 = 600
0111 = 9600
1110 = 1200
*1111 = 19.2K
Po
le
s
5
-8
Po
rt
B
0000 = N/U
0001 = 1800
1000 = 75
1001 = 2000
0100 = 110
0101 = 2400
1100 = 134.5
1101 = N/U
0010 = 150
0011 = 4800
1010 = 300
1011 = N/U
0110 = 600
*0111 = 9600
1110 = 1200
1111 = 19.2K
NOTES:
* = Normal setting.
Closed = 0 = on = up.
Open = 1 = off = down.
N/U = Not used.
Table 4-8. Multibus Communication Processor
Configuration - Switch 2
Poles
Function
Description
1
Firmware test mode
*0 = disabled
1 = enabled
2
MLM diagnostic mode
*0 = disabled
1 = enabled
3
INFI-NET diagnostics
*0 = disabled
1 = enabled
4-6
Unused
7
NVRAM installed
0 = NVRAM not installed
*1 = NVRAM installed
8
RAM component size
0 = 32 kb
×
8 (512 kb)
*1 = 128 kb
×
8 (2 Mb)
NOTES:
* = Normal setting.
Closed = 0 = on = up.
Open = 1 = off = down.