INSTALLING SOFTWARE
DOS UTILITIES - EXAMPLES
I-E96-107-2N
A - 9
•
When the computer reboots, the unique PCI Integrated
Ethernet Interface address will be enabled and displayed.
For the XU series you must return to the page in the setup
menu where you enabled the interface. For the XM series, it
is displayed on the summary of the computer's hardware.
Record this address in the
When you install both the QNX Operating System and the
OIS12 software, select the NE2100 Ethernet driver. Using the
NE2100 Ethernet driver will not require an entry for the IRQ or
I/O address.
WinStar-16
The WinStar-16 is an ISA bus, NE1000/NE2000 compatible
Ethernet card. All configuration settings are done using a
DOS-based setup program supplied with the card. Refer to the
WinStar-16
manual for details on the settings. Use the following
procedure to start the DOS-based setup program and to config-
ure the WinStar 16 Ethernet card as shown in Table
•
Boot the PC into DOS.
•
Place the WinStar-16 Utility disk in the floppy drive.
•
Enter the command:
a:\WSPNP.
•
Select the menu item
View Current Configuration
from the
Main menu.
•
Record the Ethernet address in
for this node.
•
Verify the Ethernet's card settings as listed in Table
. If
they do not match, return to the Main menu, select the
menu item
Setup WINSTAR-16
and modify the configura-
tion accordingly.
Table A-5. WinStar-16 Configuration
Option
Recommended Settings: OIS12 Server
Operating Mode
Jumperless
Ethernet Address
1
***************
Medium Type
2
Auto Detect
Full-duplex
Disabled
I/O Base
3
340h
Interrupt
4
10
Boot ROM
No Boot ROM
NOTES:
1. The 12-digit Ethernet address is unique per card.
2. The card's firmware will automatically detect the type of cable connected to the card. You can
also specifically select either 10BaseT or 10Base2.
3. Alternative I/O Base addresses available are 320 and 360. Before using address 360, check that
the parallel port is not assigned to address 378.
4. Alternative Interrupt is 5.