INSTALLATION
SAFETY CONSIDERATIONS
I-E96-107-2N
3 - 3
SAFETY CONSIDERATIONS
Do not remove or install circuit boards with power applied to
the OIS/OIC. The circuit board may be damaged. Remove AC
power to all AC wiring when removing or connecting AC wires
to prevent personal injury and equipment damage. Remove DC
power to all DC wiring when removing or connecting DC wires
or circuit boards to prevent damage to equipment.
IIOIS12/IIOIC12 PHYSICAL DESCRIPTION
The dimensions of the Operator Interface Station (OIS) and
Operator Interface Console (OIC) are approximately 110-centi-
meters (43-inches) high, by 72-centimeters (28-inches) wide,
by 118-centimeters (46-inches) deep. It has front and rear
swing-out doors with individual locks. The front door has slot-
ted openings to accommodate the air intake for the unit’s
internal cooling system. The unit has a stabilizer which must
be fastened to the front of the cabinet when the OIS/OIC is not
secured to the floor. The 6.4-centimeters (2.5-inches) diameter
cable entry is located at the bottom right rear of the unit. The
cabinet dimensions are shown on
Figure
IIOIS12/IIOIC12 SETUP AND PHYSICAL INSTALLATION
Before the OIS/OIC is set into place in a control room applica-
tion, insure that the floor is level in the area where the cabi-
nets will be set.
1. Adjust the leveling screws on all cabinets and connecting
tables until the CRT bezel of each cabinet lines up. The leveling
screws adjust 2.65 centimeters (1.05 inches). The dimensions
for the leveling studs are shown on Figure
Figure 3-1. IIOIS12/IIOIC12 Cabinet Dimensions
GS940119
DIMENSIONS
83.04
109.01
71.12
72.46
107.27
32.693
42.918
28.00
28.527
42.234
CENTIMETERS
INCHES