INTRODUCTION
I-E96-202B
C - 1
INTRODUCTION
The IMMFP02 Multi-Function Processor Module can use the
NTMP01 termination unit for termination. Jumpers on the
NTMP01 unit configure the two RS-232-C ports for data termi-
nal equipment (DTE) or data communication equipment (DCE).
One of the RS-232-C ports can be configured as an RS-485
port. Refer to the NTMP01 product instruction for complete
information on applications.
Figures
through
show the jumper configurations for
jumpers J1 and J2. Figure
shows the jumper configura-
tions for jumpers J3 through J10. Figure
shows the
jumper configurations for jumpers J14 through J17. Figure
shows the NTMP01 connector assignments and jumper
locations. Figure
shows the cable connections for redun-
dant MFP modules. Figure
shows the cable connections for
a single MFP module.
Jumpers J11 and J12 are storage posts for extra jumpers.
Jumper J13 is normally set with pins one and two connected.
This connects the cable shielding pin of connector P7 to chas-
sis ground. Jumper J18 configures the terminal serial port for
RS-485 operation when pins one and two are connected and
connector P7 is used instead of P5.
Figure C-1. DTE Jumper Configuration for NTMP01
Termination Unit
RXD
TP25051B
RXD-A
TXD-A
TXD
CTS-A
CTS
RTS-A
RTS
DB25-3
DB25-2
DB25-4
DB25-5
J1 AND J2
1
2
3
4
5
6
7
8
9
10
11
12
APPENDIX C - NTMP01 TERMINATION UNIT CONFIGURATION