INSTALLATION
INSTALLING THE MODULE
3 - 10
I-E96-202B
®
2. Check for -30 VDC with respect to system common at the
-30 VDC faston.
3. If -30 VDC is present, set jumper J5 and dipswitch SW3 to
the appropriate positions.
Before installing the MFP module:
1. Check all module dipswitch and jumper settings (normal
and special operation)
2. Insure that respective module cables are attached to their
proper slot in the module mounting unit backplane.
To install the MFP module:
1. Guide the top and bottom edges of the module along the
top and bottom rails of their assigned slot in the module
mounting unit.
2. Push on the faceplate until the rear edge of the module is
firmly seated in the backplane connectors.
NOTE: If installing the MFP module under power, verify the status
LED illuminates red momentarily and then illuminates green. If these
events do not occur, refer to
for corrective action.
3. Turn the 2 latching screws 1/2 turn to lock the module in
place. The module is locked in place when the open end of the
slots on the latching screws face the center of the faceplate.
CAUTION
To avoid potential module damage, evaluate your system for
compatibility prior to module installation. This module uses
connections to the module mounting unit backplane that
served other functions in early Network 90 systems.
ATTENTION
Pour éviter d'endommager des modules, évaluez la compatibil-
ité de votre systéme avante de les y brancher. L'usage que fait
ce module de certaines connexions au fond de panier du châs-
sis de montage différe de l'assignation prévue par le systéme
Network 90 original.