INSTALLATION
UNPACKING AND INSPECTION
3 - 2
I-E96-202B
®
7.
Use a Grounded Wrist Strap
. Connect the wrist strap to
the appropriate grounding plug on the power entry panel. The
grounding plug on the power entry panel is connected to the
cabinet chassis ground.
8.
Do Not Use Lead Pencils to Set Dipswitches
. To avoid
contamination of dipswitch contacts that can result in unnec-
essary circuit board malfunction, do not use a lead pencil to
set a dipswitch.
UNPACKING AND INSPECTION
1. Examine the hardware immediately for shipping damage.
2. Notify the nearest Bailey Controls sales office of any such
damage.
3. File a claim for any damage with the transportation com-
pany that handled the shipment.
4. Use the original packing material and container to store the
hardware.
5. Store the hardware in an environment of good air quality,
free from temperature and moisture extremes.
SETUP AND PHYSICAL INSTALLATION
This section explains how to configure and install the MFP
module. After installing the MFP module, a function block con-
figuration must be created to define the functions the module
will perform. This configuration can be created in the module
itself or can be created using a configuration tool (e.g., CAD/
TXT, EWS) and then downloaded to the module.
The MFP module has two configurable dipswitches and five
jumpers. Each dipswitch has eight poles. See Figure
for
dipswitch and jumper locations. Dipswitch SW3 sets the bus
mode and module address. Dipswitch SW4 sets module options
and special operations (refer to
of this sec-
tion). Jumpers J1 through J5 are for special applications.
Dipswitch poles marked unused in tables must be kept in the
zero position. The MFP module may not operate properly if these
dipswitches are set to the one position. Since factory settings do
not reflect default settings, it is imperative that all dipswitch set-
tings be checked before putting the module into operation.
Dipswitch SW3 Settings
Dipswitch SW3 sets the bus mode and address of the MFP
module. The MFP module can have an address from zero
through 31. Address zero and one should not be used because