INSTALLATION
SETUP AND PHYSICAL INSTALLATION
I-E96-202B
3 - 3
other MFP modules will not be able to import data from this
MFP module. All MFP modules within a process control unit
must communicate on the same communication highway
(module bus or Controlway). Table
each dipswitch pole. Table
shows some sample dipswitch
settings. For quick reference, record dipswitch settings in the
user setting portion of the table.
NOTE: Module addresses of redundant MFP modules must be iden-
tical. All modules within a process control unit must be set to com-
municate on either the Controlway or module bus.
Figure 3-1. IMMFP02 Module Layout
P 3
P 2
1 2 3 4 5 6 7 8
P 1
T P 5 03 3 0B
O N
1 2 3 4 5 6 7 8
O N
S W 4
J U M P E R S A N D P O S T S
M A C H IN E F A U L T T IM E R
J U M P E R P O S T S
S W 3
J 1
J 2
J 3
J 4
J 5
-3 0 V D C S Y S T E M
(D E F A U L T )
C O N T R O L W A Y
J 5
J 5
Table 3-1. IMMFP02 Dipswitch SW3 Settings
Pole
Setting
Function
User
Setting
1
0
Normal run.
^
1
Invoke diagnostics using dipswitch
SW4.
2
0
Unused. Do not change setting.
3
1
0
Controlway (1 Mbaud) mode.
^
1
Module bus (83.3 kbaud) mode.
4 - 8
0 - 31
Controlway or module bus address.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF; shaded areas designate mandatory pole settings.
1. Set jumper J5 for the same mode set by this dipswitch pole.