OPERATING PROCEDURES
LED INDICATORS
4 - 2
I-E96-202B
®
Front Panel LEDs One through Eight
These LEDs indicate MFP module error codes. In redundant
configurations, these LEDs also designate the primary MFP
module and the secondary MFP module. LEDs seven and eight
illuminate on the primary module. Only LED eight illuminates
on the secondary module. If an error occurs, the status LED
may start flashing or change from green to red and LEDs one
through eight illuminate in a certain sequence. This sequence
corresponds to an error code. Refer to Table
to interpret the
error code. Please note that LEDs one through eight illuminate
during module start-up. This is normal operation and means
that the module is not yet on-line.
Red/Green Status LED
The status LED is a two-color (red and green) LED. It shows the
MFP module operating condition. There are four possible oper-
ating conditions:
Off
No power is being supplied to the MFP module. The status LED
is momentarily off when the microprocessor initializes on
start-up.
Figure 4-1. IMMFP02 Front Panel LEDs
and Controls
TP50347A
STOP/RESET
SWITCH
RED/GREEN
STATUS LED
IMMFP02
LEDs 1-8
1
2
3
4
5
8
7
8