INSTALLATION
PREPARING THE MODULE MOUNTING UNIT
I-E96-202B
3 - 7
three together to use the module on the Controlway. Refer to
Table
for more information.
NOTE: Two unlabeled jumper pins are located at the front of the
MFP circuit board. These are for Bailey Controls development per-
sonnel only. They are used to disable the machine fault timer circuit.
If this function is disabled (jumper pins connected) and a problem
develops in the MFP module, the module will not halt which may
result in configuration corruption and unpredictable module outputs.
PREPARING THE MODULE MOUNTING UNIT
Preparing the module mounting unit consists of identifying the
proper slots, installing the required dipshunts, and verifying
the Controlway or module bus cable is installed.
Dipshunts
Verify that 24-pin dipshunts are in place between all module
slots on the I/O expander bus associated with one MFP mod-
ule. One dipshunt goes between each module slot to maintain
continuity. Remove any dipshunts that would connect the MFP
module to any module slots not associated with the MFP mod-
ule.
Table 3-5. IMMFP02 Jumpers J1 through J5 Settings
Jumper
Setting
Function
User Setting
J1
1-2
Factory setting. Do not change this setting.
J2
1-2
J3
1-2
J4
1-2
J5
1-2
Disconnects Controlway for operation in module mounting units
that have -30 VDC (early Network 90).
2-3
Allows operation in module mounting units that have Controlway
communication. This setting must be used if dipswitch SW3
selects the Controlway.
NOTE: Shaded areas designate mandatory jumper settings.
WARNING
Disconnect power before installing dipshunts on the module
mounting unit backplane. Failure to do so will result in contact
with cabinet areas that could cause severe or fatal shock.
AVERTISSEMENT
Interrompez l'alimentation avante d'installer des dipshunts sur
le fond de panier du châssis de montage des modules. Sinon,
tout contact avec cette zone entraîne des risques d'électrocu-
tion sérieuse ou fatale.