INSTALLATION
INSTALLING THE MODULE
I-E96-202B
3 - 9
2. Install the termination unit on the termination unit panel
and secure into place.
3. Connect the hooded end of the NKTU01 or NKTU11 cable to
the rear of the module mounting unit slot assigned to the MFP
module.
4. Connect the other end of the cable to the P1 connector on
the termination unit. For redundant modules, connect the
other end of the cable to the P2 connector on the termination
unit.
NIMP01 or NIMP02 Termination Module Installation
1. Configure the jumpers on the termination module. Refer to
for quick reference or to the appropriate instruc-
tion for detailed information on jumper settings and applica-
tions.
2. Connect one end of the NKTU02 or NKTU12 cable to the
rear of the termination mounting unit.
3. Connect the other end of the cable to the rear of the module
mounting unit slot assigned to the MFP module.
4. Push the termination module into the termination mount-
ing unit until it seats in the termination module connector.
INSTALLING THE MODULE
To determine if the module mounting unit uses -30 VDC:
1. Locate the -30 VDC faston. It is the second faston from the
top when viewing the module mounting unit from the rear.
CAUTION
Never operate the MFP module with the machine fault timer cir-
cuit disabled (jumper pins connected). Unpredictable module
outputs and configuration corruption may result. The unpre-
dictable module outputs may damage control equipment con-
nected to the MFP module.
ATTENTION
N'utilisez jamais un module MFP sans l'usage de sa minuterie
de détection de défaillance (MFT) (c'est à dire avec le cavalier
en place). Les sorties du module pourraient prendre des
valeurs ou des états imprévisibles, et la configuration pourrait
être corrompue. Le comportement imprévisible des sorties
pourrait endommager le matériel de commande relié au mod-
ule MFP.