INSTALLATION
SETUP AND PHYSICAL INSTALLATION
I-E96-202B
3 - 5
Special Operations
The special operations feature provides a mechanism to config-
ure the MFP module to do a one-time special operation rather
than entering its normal mode of operation. Steps 1 through 8
explain how to set the MFP module for special operations and
reset it for normal operation. Table
shows the dipswitch
settings and explains each special operation.
7
0
Normal operation.
1
Initializes NVRAM (erase configuration) memory. To enable this
function, open the pole and insert the module into the module
mounting unit. When front panel LEDs 1, 2, and 4 are ON, remove
the module, put the pole in the closed position, and insert the mod-
ule. The module is now ready to be configured.
NOTE:This position must remain CLOSED for normal operation.
8
0
Primary MFP module.
1
Redundant MFP module.
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF; shaded areas designate mandatory pole settings.
1. Disabling the checksum routine is sometimes done by development personnel and should never be done for normal operation. The check-
sum routine provides additional module integrity and should be active whenever the module is controlling a process.
2. Leaving this option enabled causes the configuration to be compacted every time the module is reset thereby increasing the startup time.
This increase becomes more substantial as the size of the configuration increases. Therefore, do not leave this option enabled longer than
necessary. Disabling this option stops any further compacting operations. It does not uncompact any previously compacted configuration.
Table 3-3. IMMFP02 Dipswitch SW4 Normal Operation Settings
(continued)
Pole
Setting
Function
User Setting
® Registered trademark of Elsag Bailey Process Automation.
Table 3-4. IMMFP02 Dipswitch SW4 Special Operation Settings
Special
Operation
Dipswitch Position
Description
1
2 3 4 5 6 7 8
0
1
0
0
0
0
0
0
0
Reserved.
Do not use this setting. Using this setting may
cause the module to operate improperly.
1
1
0
0
0
0
0
0
1
Reserved for future options. Not used at this time.
2
1
0
0
0
0
0
1
0
Initializes NVRAM configuration space and format the module
for Plant Loop operation.
3
1
0
0
0
0
0
1
1
Reserved.
Do not use this setting. Using this setting may
cause the module to operate improperly.
4
1
0
0
0
0
1
0
0
Enables INFI-NET
®
protocol. This allows exception reporting
from function blocks numbered 1024 or greater.
5
1
0
0
0
0
1
0
1
Permit segment modification (allows change to segment
scheme configured with function code 82, specification S1).
6
1
0
0
0
0
1
1
0
Enable time stamping. This operation instructs the MFP mod-
ule to generate time information with point data. It is applica-
ble only to INFI-NET systems.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.