INSTALLATION
SETUP AND PHYSICAL INSTALLATION
3 - 4
I-E96-202B
®
Dipswitch SW4 Settings
Dipswitch SW4 enables the selection of a variety of module
options. Refer to Table
for an explanation of the option set-
tings. Refer to
of this instruction for the diagnostic
dipswitch setting information.
NOTE: Poles 1 through 7 on redundant MFP modules must be set
to the same values.
Table 3-2. Example IMMFP02 Module Address Settings
Address
Example
Dipswitch Position
(Binary Value)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
7
0
0
1
1
1
15
0
1
1
1
1
User
Setting
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table 3-3. IMMFP02 Dipswitch SW4 Normal Operation Settings
Pole
Setting
Function
User Setting
1
0
Disable special operations.
1
Enable special operations. Refer to
section for explanation.
2
0
Disable on-line configuration.
1
Enable on-line configuration.
3
0
Perform NVRAM checksum routine.
1
Inhibit NVRAM checksum routine.
1
4
0
Perform ROM checksum routine.
1
Inhibit ROM checksum routine.
1
5
0
Reserved for future options. Use this setting for normal operations
even though it performs no function at this time.
1
Reserved for future options. Do not use this setting.
6
0
Normal operation.
1
The compact configuration function moves configured function
blocks to the top of the NVRAM memory while moving free space
to the bottom. This condenses the configured function blocks while
providing the largest possible area of contiguous unconfigured
function blocks to the user. To enable this function, open the pole
and insert the module into the module mounting unit. After a short
time period (directly proportional to the configuration size) the
module will return to the mode it was in prior to being reset for the
compact operation.
2