5-5
Chapter 5. ADVANCED OPERATION
Display
item
Item Description
Setup Item and
Description
Factory
Setting
Remarks
C-0
9
External 3-way
switching function
0: Not used
1: Switching of operating
mode 1
2: Switching of SP No.
3: Switching of totalizing
operation
4: Switching of analog I/O volt-
age range
(simultaneous external
switching of
C-05
and
C-06
)
5: Switching of operating
mode 2
0
External inputs OPEN/GND/5 V are
switched as shown below.
For details on wiring, see page 3-10.
1: Control/fully closed/fully open
Table in note 7 on P. 5-9 (for
details on operation)
2: SP-0/SP-1/SP-2
3: Continue count/reset count/ stop
count
4: See the table in note *
3
.
0 to 5 V/0 to 5 V/1 to 5 V
5: Fully closed/control/fully open
Table in note 7 on P. 5-9 (for
details on operation)
C-
10
External contact
1 input function
assignment
(2-way switching)
0: Not used
1: Reset totalized flow count
2: Stop totalizing flow count
3: Switching of SP No.
4: Switching of instantaneous
flow rate setup method
5: Valve forced fully closed
6: Valve forced fully open
7: Switching of slow start
operation or switching of in-
stantaneous SP ramp control
operation
8: Switching of operating
mode
(control by contact ON,
forced fully closed by con-
tact OFF)
9: Flow rate zero adjustment
10: Switching of gas type setup
11: Switching of flow rate range
12: Switching of SP ramp
13: Alarm reset
0
3: For details on how to switch
three or more SP Nos., see the
description of the multi-setup
(page 4-5).
4: The
C-03
(analog/digital) setting
is is switched over when the con-
tacts turn on.
7: “Slow start ON” must be selected
in
C-
1
7
(Slow start when the
contact is ON).
Similarly, in case of SP ramp con-
trol, "SP ramp control 1 or 2" must
be selected in
C-
27
.
(Ramp control when the contact
is ON.)
5, 6, 8: If the forced fully closed and
fully open are input from two
sources at the same time,
both inputs become invalid.
9: Set the operation mode to full
close or set the flow rate to zero
and perform the contact ON
operation for a minimum of 10
seconds.
See page 6-2 for the details.
10:
C-
18
becomes active by contact
OFF and
C-
26
becomes active
by contact ON.
11:
C-
24
becomes active by contact
OFF and
C-
25
becomes active
by contact ON.
12: Parameter setup ramp 1 is se-
lected when the contact is OFF.
Ramp 2 is selected when the con-
tact is ON.
13: All alarm detections are cancelled
while the contact ON is being
continued.
C-
1
1
External contact
2 input function
assignment
(2-way switching)
0
C-
12
External contact
3 input function
assignment
(2-way switching)
0